ABB electrical accessory WA39KK51 2CPX056206R9999
- BrandABB
- SeriesWA39KK51
- Depth215 mm
- Max. cross section outgoing cable120 mm²
- Max. cross section connection cable120 mm²
- Nominal voltage (Un)415 V
- Rated insulation voltage Ui690 V

Transformer meter cabinet ABB 2CPX056206R9999: nominal voltage (Un) 415 V, rated frequency 50 Hz, mounting method surface mounted/partially recessed mounted, rated impulse voltage 6 kV. Transformer meter cabinet. Dimensions 800 × 1400 × 215 mm (W × H × D).
| Series | WA39KK51 |
|---|---|
| Electrical | |
| Max. cross section outgoing cable | 120 mm² |
| Max. cross section connection cable | 120 mm² |
| Nominal voltage (Un) | 415 V |
| Rated insulation voltage Ui | 690 V |
| Resistance to current surges | 25 kA |
| Continuous current Inc | 250 A |
| Rated frequency | 50 Hz |
| Rated impulse voltage | 6 kV |
| Rated short-time withstand current Icw | 25 kA |
| Number of poles busbar (connection space, power side) | 5-pole |
| Number of switching device panels | 1 |
| Meter equipped with control cable duct | No |
| Meter equipped with push-in distribution terminal block | No |
| Termination point meter location | Yes |
| Suitable for metering transformer conversion board | No |
| Disconnecting point, system side | Switch disconnector (low voltage) |
| Disconnecting point, power side | Knife blade fuse holder |
| With metering transformer conversion board | No |
| Test terminal, number of poles | 16 |
| Lower current feed | With busbar |
| With power supply connector | Yes |
| Mechanical | |
| Depth | 215 mm |
| Width | 800 mm |
| Height | 1400 mm |
| Color | White |
| Number of doors | 2 |
| Number of indirect meters | 1 |
| Number of locks | 1 |
| RAL colour number | 9016 |
| Impact resistance | IK07 |
| Suitable for outdoor installation | No |
| Mounting method | Surface mounted/partially recessed mounted |
| With mounting plate | No |
| Operating conditions | |
| Operating temperature | 5–25 °C |
| IP protection rating | IP31 |
| Pollution degree | 3 |
| Other | |
| Electromagnetic compatibility (EMC) | Category B |
| Number of fields | 3 |
| Meter equipped with optical communication head | No |
| Overvoltage protection | Prepared |
| Earthing system | TN-S |
| Rated load factor RDF | 1 |
| Equipment of additional transformer meter compartment | Test terminal |
| Equipment of transformer compartment | Busbar |
| With primary wiring | Yes |
| With secondary wiring | Yes |