ABB MCCB component XT7 1000A 3p 1SDA103446R1
- BrandABB
- SeriesXT7
- Rated current In1 kA
- Power loss37 W
- Setting range of overload protection device0.4–1 kA
- Instantaneous short-circuit release setting range1–10 kA
- Short-time delayed short-circuit release range1–10 kA
All parameters ›
Description
C.BREAKER TMAX T7S 1000 UL/CSA FIXED THREE-POLE WITH FRONT TERMINALS AND STORED ENERGY OPERATING MECHANISM AND SOLID-STATE RELEASE IN AC EKIP DIP LSIG
Technical data
| Series | XT7 |
|---|
| Electrical |
|---|
| Rated current In | 1 kA |
|---|
| Power loss | 37 W |
|---|
| Short-time delayed short-circuit release range | 1–10 kA |
|---|
| Rated voltage | 600 V |
|---|
| Rated continuous current Iu | 1 kA |
|---|
| Number of poles | 3 |
|---|
| Main circuit connection type | Front side |
|---|
| Main electrical circuit connection type | Screw connection |
|---|
| With built-in undervoltage release | No |
|---|
| Mechanical |
|---|
| DIN rail mounting (O-type) optional | No |
|---|
| Suitable for DIN-rail mounting | No |
|---|
| Operating conditions |
|---|
| IP protection rating | IP20 |
|---|
| Other |
|---|
| Setting range of overload protection device | 0.4–1 kA |
|---|
| Instantaneous short-circuit release setting range | 1–10 kA |
|---|
| Complete device with protection block | Yes |
|---|
| Design | Built-in device fixed built-in technique |
|---|
| Motor drive optional | Yes |
|---|
| Trip indicator present | No |
|---|
| Control element type | Wing knob |
|---|
| Built-in ground fault protection | No |
|---|
| Built-in motor drive | No |
|---|