Legrand DPX moulded case circuit breaker 3P 500 A 70 kA electronic trip unit IP30 DPX3 630 S10 422843
- BrandLegrand
- SeriesDPX 250 1600
- Ultimate breaking capacity Icu70 kA
- Depth170 mm
- Rated current In500 A
- Width270 mm
- Height150 mm
Legrand DPX moulded case circuit breaker 3P, 500 A, 70 kA, electronic trip unit, IP30 (catalogue number 422843), breaking capacity Icu 70 kA, overload release setting range 0.2…1 A. Use: for TH rail mounting. Design: optional DIN TH rail mounting, supplied with protection device, optional motor operator. Main parameters: rated current In 500 A; number of poles 3; breaking capacity Icu 70 kA; overload release setting range 0.2…1 A; number of auxiliary changeover contacts 1; voltage type AC; width 270 mm, height 150 mm, depth 170 mm. A moulded case circuit breaker is used to switch distribution circuits and protect them against overloads and short circuits.
| Series | DPX 250 1600 |
|---|---|
| Ultimate breaking capacity Icu | 70 kA |
| Depth | 170 mm |
| Rated current In | 500 A |
| Width | 270 mm |
| Height | 150 mm |
| Device design | Complete device in housing |
| For TH rail mounting | Yes |
| Supply direction | From top or bottom |
| Colour | Grey |
| Number of poles | 3 |
| Number of auxiliary changeover contacts | 1 |
| Number of auxiliary NC contacts | 1 |
| Number of auxiliary NO contacts | 1 |
| Labelling area | Yes |
| Impact resistance | IK07 |
| Optional DIN (TH) rail mounting | Yes |
| Optional motor operator | Yes |
| Terminal marking | No |
| Terminal cross-section (min-max) | 90 - 150 mm² |
| Actuator type | Switch |
| Connection cable type | Flexible or rigid |
| Voltage type | AC |
| Main contact connection type | Screw connection |
| Degree of protection (IP) | IP30 |
| Storage temperature (min-max) | -40 - 85 °C |
| Main circuit terminal location | Rear |
| Supplied with protection device | Yes |
| Integrated motor operator | No |
| Frequency range (min-max) | 50-60 Hz |
| Rated voltage range (min-max) | 230-400 V |
| Short-time delay release setting range (min-max) | 1.5 - 10 A |
| Overload release setting range (min-max) | 0.2 - 1 A |
| Operating temperature range (min-max) | -5 - 70 °C |
| Contains battery and/or accumulator | No |
| With trip indicator | No |
| With integrated undervoltage release | No |
| Integrated earth fault protection | No |
| Rated short-circuit breaking capacity Icu at 400 V, 50 Hz | 70 kA |
| Rated uninterrupted current Iu | 500 A |
Technical data according to the manufacturer's documentation.
Instructions and safety information — in the manufacturer's documents above or on the manufacturer's website.
We use cookies to ensure the website works properly and to give you a better experience. Privacy Policy