Region and language

Prices include VAT of the delivery country.

Delivery and paymentsConfiguratorsArticles +48 793 996 171
Photo coming soon

Legrand DPX3 1600 moulded case circuit breaker 3P 630 A 70 kA IP30 Sg 422419

Ref. no. 422419 (4224 19)LegrandEAN 3414970381859
  • BrandLegrand
  • SeriesDPX3 1600
  • Ultimate breaking capacity Icu70 kA
  • Rated current In630 A
  • Battery or accumulatorBattery
  • Battery weight (g) for Type 11.1
  • Device designPermanently installed device

All parameters ›

Description

Legrand DPX3 1600 moulded case circuit breaker 3P, 630 A, 70 kA, IP30, reference 422419, overload release setting range 252…630 A, short-circuit release setting range 15000 A. A moulded case circuit breaker is used to switch distribution circuits and protect them against overloads and short circuits. Key parameters: rated current In 630 A; number of poles 3; breaking capacity Icu 70 kA; overload release setting range 252…630 A; short-circuit release setting range 15000 A; rated voltage range 220…690 V; short-time delay release setting range 378…6300 A; main contact connection type screw connection. Features: integrated earth-fault protection, with trip indicator, with integrated undervoltage release.

Technical data

SeriesDPX3 1600
Ultimate breaking capacity Icu70 kA
Rated current In630 A
Battery or accumulatorBattery
Battery weight (g) for Type 11.1
Device designPermanently installed device
For TH rail mountingNo
Number of batteries1
Number of poles3
Number of auxiliary changeover contacts3
Type 1 number2
Optional DIN (TH) rail mountingNo
Optional motor operatorYes
IEC designationCR1616
Actuator typeSwitch
Main contact connection typeScrew connection
Battery type/technologyLithium
Degree of protection (IP)IP30
Total weight of the batteries (Type 1)2.2
Adjustment typePortable (standard format)
Type 1 locationProduct contains a battery
Main circuit terminal locationFront
Supplied with protection deviceYes
Integrated motor operatorNo
Rated voltage range (min-max)220-690 V
Short-time delay release setting range (min-max)378-6300 A
Overload release setting range (min-max)252-630 A
Short-circuit release setting range (min-max)15000-15000 A
Contains battery and/or accumulatorYes
With trip indicatorYes
With integrated undervoltage releaseYes
Integrated earth fault protectionYes
Rated short-circuit breaking capacity Icu at 400 V, 50 Hz70 kA
Rated uninterrupted current Iu630 A

Technical data according to the manufacturer's documentation.

Documents

Related products

Product safety information (GPSR)

Manufacturer
Legrand SNC, 128 avenue du Maréchal de Lattre de Tassigny, 87045 Limoges Cedex, France · www.legrand.com
Responsible person in the EU / importer
Legrand Polska sp. z o.o., ul. Waryńskiego 20, 57-200 Ząbkowice Śląskie, Poland · www.legrand.pl

Instructions and safety information — in the manufacturer's documents above or on the manufacturer's website.