Power circuit-breaker for trafo/generator/installation protection ABB E6.2H 5000 Ekip G Hi-Touch LSIG 3p F 1SDA071270R1

Power circuit-breaker for trafo/generator/installation protection ABB E6.2H 5000 Ekip G Hi-Touch LSIG 3p F 1SDA071270R1

Ref. no. 1SDA071270R1ABBEAN 8015644751203
  • BrandABB
  • SeriesE6.2H 5000 Ekip G Hi-Touch LSIG 3p F HR
  • Power loss483 W
  • Setting range of overload protection device2–5 kA
  • Instantaneous short-circuit release setting range7.5–75 kA
  • Short-time delayed short-circuit release range3–50 kA
  • Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz100 kA

All parameters ›

Description

Power circuit-breaker for trafo/generator/installation protection ABB 1SDA071270R1: number of auxiliary changeover contacts 4, number of poles 3. This power circuit-breaker series includes several frame sizes for switchgear with compact dimensions and high ratings. It allows busbars to be designed with optimized lengths and cross-sections. Power circuit breaker for protecting and switching power circuits in low-voltage switchboards. Degree of protection IP30.

Technical data

SeriesE6.2H 5000 Ekip G Hi-Touch LSIG 3p F HR
Electrical
Power loss483 W
Short-time delayed short-circuit release range3–50 kA
Rated ultimate short-circuit breaking capacity Icu at 400 V, 50 Hz100 kA
Rated voltage690 V
Rated continuous current Iu5 kA
Number of poles3
Number of auxiliary changeover contacts4
Main circuit connection typeBack side
Main electrical circuit connection typeScrew connection
With built-in undervoltage releaseNo
Mechanical
DIN rail mounting (O-type) optionalNo
Suitable for DIN-rail mountingNo
Operating conditions
IP protection ratingIP30
Other
Setting range of overload protection device2–5 kA
Instantaneous short-circuit release setting range7.5–75 kA
Complete device with protection blockYes
DesignBuilt-in device fixed built-in technique
Motor drive optionalYes
Trip indicator presentYes
Control element typePush button
Built-in ground fault protectionYes
Built-in motor driveNo