··PolskiEnglish
Region and language

Prices include VAT of the delivery country.

CatalogueDelivery and paymentsRequest for quoteConfiguratorsArticles +48 793 996 171
Published: ·16 min read

CPR cable Euroclasses: Aca–Fca, s, d, a classes and the DoP

What Eca, Dca, Cca and B2ca-s1,d0,a1 on a cable drum mean, how they are tested to EN 50399 and EN 60332-1-2, and how to read the DoP and CE label.

Contents
Reaction-to-fire classes, a cable in flame with smoke and burning droplets, acidity and declaration of performance

Since July 2017, every cable placed on the EU market for permanent installation in buildings has had to carry a declared reaction-to-fire class. That is why drum labels now show codes such as "Eca" or "B2ca-s1,d0,a1", backed by a Declaration of Performance. Here is what each letter means, which tests stand behind it and how to read the label so you can match a cable to the building it is going into.

Where cable Euroclasses come from

The legal basis is Regulation (EU) No 305/2011, the Construction Products Regulation (CPR), which is being progressively replaced by Regulation (EU) 2024/3110. Cables installed permanently in construction works are construction products, and the harmonised standard that applies to them is EN 50575 – power, control and communication cables for general applications in construction works subject to reaction-to-fire requirements. The coexistence period ended on 1 July 2017; from then on, manufacturers have had to issue a Declaration of Performance (DoP) and CE-mark the product.

The classes and their criteria are set out in Commission Delegated Regulation (EU) 2016/364, and the classification procedure in EN 13501-6. One point matters above all: a Euroclass describes how the cable behaves as fuel in a fire – flame spread, heat release, smoke, droplets and acidity. It says nothing about whether the circuit keeps working in a fire. That is fire resistance, tested by different methods (for example EN 50200) and marked with symbols such as PH or E30/E90.

Main classes: Aca to Fca

The seven main classes run from an essentially non-combustible product to one whose performance has not been determined. Classes B1ca to Eca require at least the single-cable test to EN 60332-1-2 (vertical sample, 1 kW burner); class Aca only EN ISO 1716. Classes B1ca to Dca also require the bunched-cable test to EN 50399.

ClassTestsKey criteria (Reg. 2016/364)Typical use in practice
AcaEN ISO 1716gross heat of combustion PCS ≤ 2.0 MJ/kge.g. mineral-insulated cables, rarely seen
B1caEN 50399 (30 kW burner) + EN 60332-1-2FS ≤ 1.75 m; THR ≤ 10 MJ; peak HRR ≤ 20 kW; FIGRA ≤ 120 W/shighest-demand buildings, tunnels
B2caEN 50399 (20.5 kW) + EN 60332-1-2FS ≤ 1.5 m; THR ≤ 15 MJ; peak HRR ≤ 30 kW; FIGRA ≤ 150 W/sescape routes, high-rise and public buildings
CcaEN 50399 (20.5 kW) + EN 60332-1-2FS ≤ 2.0 m; THR ≤ 30 MJ; peak HRR ≤ 60 kW; FIGRA ≤ 300 W/soffices, schools, hospitals, cable risers
DcaEN 50399 (20.5 kW) + EN 60332-1-2THR ≤ 70 MJ; peak HRR ≤ 400 kW; FIGRA ≤ 1300 W/slower-risk and industrial buildings
EcaEN 60332-1-2flame propagation on sample ≤ 425 mmstandard PVC wiring in housing
Fca–no performance determinednot for fixed installation where a class is required

Abbreviations: FS – flame spread on the ladder, THR – total heat release over 1200 s, HRR – heat release rate, FIGRA – fire growth rate index.

Additional classes: s, d, a

For B1ca, B2ca, Cca and Dca the manufacturer also declares three additional classifications. They do not exist for Eca and Fca, which is why those cables show the class letter only.

  • s – smoke (measured in EN 50399, plus EN 61034-2 for s1a/s1b): s1 means total smoke production TSP ≤ 50 m² and peak smoke production rate SPR ≤ 0.25 m²/s; s1a adds light transmittance ≥ 80% in the EN 61034-2 cube, s1b between 60% and below 80%; s2 means TSP ≤ 400 m² and SPR ≤ 1.5 m²/s; s3 is anything that misses s1 and s2.
  • d – flaming droplets: d0 – no flaming droplets within 1200 s; d1 – no droplets burning for longer than 10 s; d2 – everything else.
  • a – acidity of combustion gases to EN 60754-2: a1 – conductivity < 2.5 µS/mm and pH > 4.3; a2 – conductivity < 10 µS/mm and pH > 4.3; a3 – everything else.

In practice, a1 is achieved by halogen-free cables. A PVC cable normally ends up as a3 because it releases hydrogen chloride when burning. Halogen-free materials are covered in our article on halogen-free (HF) cables.

How the EN 50399 test works

EN 50399 tests a bundle of cables fixed to a vertical ladder inside a test chamber several metres tall. A gas burner attacks the bottom of the bundle for 20 minutes (1200 s) while instruments in the exhaust duct measure heat and smoke; the laboratory also records how far the cables are damaged and whether flaming droplets fall. B1ca uses the stronger 30 kW burner, while B2ca, Cca and Dca use 20.5 kW. The number of cable lengths on the ladder depends on the cable diameter, so thin and thick cables are assessed with a comparable amount of combustible material.

The result applies to a specific cable design. The same type name (YDY or NHXH, for instance) can therefore carry different Euroclasses from two manufacturers – the DoP decides, not the type designation.

Which classes are used in Poland

Polish building regulations, including the regulation on the technical conditions for buildings (WT), do not assign a single cable Euroclass to each building type; detailed requirements follow from the WT and fire-safety agreements. The class is set by the designer, often together with a fire-safety expert and based on the fire scenario, the client's requirements or the insurer's. Common design practice looks like this:

  • Eca – single-family houses and flats, circuits run in plaster or conduit.
  • Dca – industrial halls and warehouses with few occupants, lightly loaded cable routes.
  • Cca-s1,d1,a1 or similar – public buildings, offices, schools, hospitals, vertical risers.
  • B2ca-s1a,d1,a1 or higher – escape routes, high-rise buildings, venues with many occupants, tunnels.

Densely packed cable trays add fuel to the route, so on long runs in shafts and corridors it is worth going one class higher even if the design would just about allow a lower one. Route planning is covered in our article on cable management systems.

DoP, CE marking and the drum label

The Declaration of Performance is the manufacturer's document declaring the cable's Euroclass under EN 50575. The drum or package label should show: the CE mark, the manufacturer's name and address, the product-type identifier, the DoP number, the reaction-to-fire class, the harmonised standard and – for classes that require a notified body – that body's number. The system for assessment and verification of constancy of performance depends on the class: Aca, B1ca, B2ca and Cca fall under system 1+ (notified-body certificate and surveillance of production), Dca and Eca under system 3 (type testing in a notified laboratory), and Fca under system 4.

The sheath print usually gives the type, cross-section, voltage and often the Euroclass. The complete information, however, is on the label and in the DoP – and those are the documents that belong in the as-built file.

How to choose – checklist

  1. Find the required Euroclass and the s, d and a classes in the design.
  2. Compare them with the DoP of the actual product – not with the type name or a shop description.
  3. Check that the label carries the CE mark, the DoP number and the EN 50575 reference.
  4. If the circuit must work during a fire, check fire resistance separately (PH, E30/E90) – the Euroclass does not cover it.
  5. Size the cable and choose the installation method to PN-HD 60364-5-52 – see selecting cable cross-sections.
  6. Keep the DoP and photos of the labels for the installation handover.

Cables and cable routes at automatics.pro

The Cables and wires category lists products with a declared reaction-to-fire class, and for routing them there are wire mesh cable trays from Cablofil and the rest of the cable management range. Cable designations are explained in Cables and wires in the EU, and the full range is in the shop.

Frequently asked questions

What is the difference between a cable and a wire?
In everyday practice a wire (or building wire) is a simpler product rated up to 450/750 V, while a cable has an extra protective sheath and is rated 0.6/1 kV or higher. For the CPR the distinction does not matter – both need a declared Euroclass when they are intended for permanent installation in a building.
Can an Eca-class YDY wire be used in an office building?
The regulations do not forbid it outright, but the required class is set by the design and the fire-safety agreements. For offices and public buildings designers often specify at least Cca with s1, d1 and a1.
How does B2ca differ from a fire-resistant cable?
B2ca describes reaction to fire – limited flame spread, heat and smoke. A fire-resistant cable must also keep the circuit working during a fire, which is proven by separate tests such as EN 50200 (PH classes).
Where can I find a cable's Declaration of Performance?
The DoP number is printed on the drum or package label, and the declaration itself is usually available on the manufacturer's website or on request. It is worth adding to the as-built documentation.
What does s1a, d0, a1 mean?
s1a means low smoke production with high light transmittance, d0 means no flaming droplets during the test, and a1 is the lowest acidity of combustion gases to EN 60754-2. Halogen-free cables in class B2ca or Cca typically carry this combination.

← All articles