Aluminium or Copper Cables: Comparison and Selection
When an aluminium cable makes sense and when to choose copper: minimum sizes under HD 60364-5-52, Cu vs Al resistance and the rules for joining aluminium to copper.

Aluminium is back in electrical installations for a simple reason: at large cross-sections an aluminium cable is clearly cheaper and lighter than a copper one. At the same time many electricians remember the trouble with old aluminium wiring in flats. Both pictures are true; they just apply to different uses. This article explains what the standards say, how to compare cross-sections, how to join aluminium to copper correctly and when aluminium makes sense.
Copper and aluminium: the properties that matter
The key difference is resistivity. Standard annealed copper (IACS, see the annex to EN 60228) has a resistivity of 0.017241 Ω·mm²/m at 20 °C, while electrical-grade aluminium to IEC 60889 has 0.028264 Ω·mm²/m. The ratio is 0.028264 / 0.017241 ≈ 1.64, so an aluminium conductor with the same resistance needs roughly 1.64 times the cross-section.
Aluminium is, however, more than three times lighter: a density of 2.703 g/cm³ against 8.89 g/cm³ for copper. Even allowing for the larger cross-section, an aluminium conductor of equal resistance weighs about half as much as the copper one (1.64 × 2.703 / 8.89 ≈ 0.50). Together with the metal price, this is what makes aluminium popular for power cables.
Aluminium's weak points are mostly in the connections: a hard, poorly conducting oxide layer forms quickly on its surface, the metal creeps under pressure, and in contact with copper in the presence of moisture it forms a galvanic cell. That is why the reliability of an aluminium installation comes down to the accessories and the care taken during installation.
What the standards say
Cable selection rules are set out in HD 60364-5-52. Its Table 52.2 gives minimum cross-sections: for cables and insulated conductors in fixed installations, power and lighting circuits, 1.5 mm² for copper and 16 mm² for aluminium, with a note that connectors used to terminate aluminium conductors must be tested and approved for this use. Aluminium is therefore not intended for ordinary socket and lighting circuits.
Continuous current-carrying capacities for copper and aluminium conductors are given in the Annex B tables of HD 60364-5-52, separately for PVC and XLPE insulation, installation methods and the number of loaded conductors. For a PEN conductor HD 60364-5-54 requires at least 10 mm² Cu or 16 mm² Al. Conductor construction (classes 1, 2, 5, 6) and maximum resistance are defined in EN 60228.
Comparing Cu and Al cross-sections
The simplest objective comparison is conductor resistance to EN 60228 (class 2 conductors, values at 20 °C):
| Cross-section | Cu, Ω/km | Al, Ω/km |
|---|---|---|
| 16 mm² | 1.15 | 1.91 |
| 25 mm² | 0.727 | 1.20 |
| 35 mm² | 0.524 | 0.868 |
| 50 mm² | 0.387 | 0.641 |
| 70 mm² | 0.268 | 0.443 |
| 95 mm² | 0.193 | 0.320 |
| 120 mm² | 0.153 | 0.253 |
The table shows a practical rule: an aluminium conductor with a resistance close to that of a copper one is usually one or two sizes larger. Al 25 mm² (1.20 Ω/km) roughly matches Cu 16 mm² (1.15 Ω/km), and Al 50 mm² (0.641 Ω/km) sits between Cu 25 and Cu 35 mm². Resistance governs voltage drop and losses, but current-carrying capacity must always be checked in the standard's tables for the actual installation method, not derived from the resistance table.
Worked example: a building riser
A three-phase feeder, 40 m long, design current 63 A. The voltage drop is ΔU = √3 × I × L × R (resistance at 20 °C, reactance ignored):
- Cu 25 mm²: 1.732 × 63 × 0.04 × 0.727 = 3.17 V, i.e. 0.79% of 400 V,
- Al 35 mm²: 1.732 × 63 × 0.04 × 0.868 = 3.79 V, i.e. 0.95%,
- Al 50 mm²: 1.732 × 63 × 0.04 × 0.641 = 2.80 V, i.e. 0.70%.
In terms of voltage drop, Al 35 mm² is close to Cu 25 mm², and Al 50 mm² does better. The final choice depends on the current-carrying capacity from the standard's tables, the installation conditions (in ground, in conduit, on a tray) and the protective device. When comparing cables, pair equivalents of the same construction and voltage: YAKY ↔ YKY (PVC insulation and sheath, 0.6/1 kV) or YAKXS ↔ YKXS (cross-linked polyethylene XLPE insulation, PVC sheath) in Polish designations, and NAYY ↔ NYY in German ones. The letter "A" marks an aluminium conductor. More on designations: Cables and wires in the EU.
Joining aluminium to copper
Most failures in aluminium installations start at a terminal. These rules prevent them:
- Use only accessories rated for Al. The terminal, lug or connector must carry the manufacturer's declared suitability for aluminium conductors (marked Al or Al/Cu). Terminal blocks tested to EN 60947-7-1 are intended for copper conductors, while connectors for power cables are tested to EN 61238-1.
- No direct Cu–Al contact in damp conditions. Use bimetallic Al/Cu lugs or terminals in which each conductor has its own clamping point.
- Remove the oxide and use contact paste. Clean the conductor immediately before installation and protect it with the paste recommended by the accessory manufacturer.
- Tightening torque. Tighten with a torque wrench to the value in the terminal's data sheet; because aluminium creeps, the manufacturer may recommend re-checking.
- No twisting or soldering in boxes. Make joints only in proper terminals, following the rules in Approved wire connections in junction boxes.
General requirements for durable connections are contained in section 526 of HD 60364-5-52, which requires the conductor and insulation material to be taken into account when choosing the connection method.
When aluminium makes sense and when it does not
| Application | Aluminium | Copper |
|---|---|---|
| Service connections and buried cable runs, 16 mm² and above | yes, the standard choice | possible, higher cost |
| Building risers and board feeders | yes, from 16 mm² | yes |
| Long runs to outbuildings or PV plants | yes, the benefit grows with size | yes |
| Socket and lighting circuits | no (below the standard's minimum) | yes |
| Flexible cords for movable equipment | no | yes |
Aluminium also loses out where space in the board is tight: a larger cross-section means bigger terminals and bending radii. Plan the transition to copper on an Al/Cu terminal or distribution block; practical tips are in Wiring and connections in distribution boards.
How to choose: checklist
- Al cross-section of at least 16 mm² in fixed installations.
- Current-carrying capacity checked in the HD 60364-5-52 tables for the actual installation method and correction factors.
- Voltage drop calculated from EN 60228 resistances.
- Total cost compared, including accessories (larger terminals, bimetallic lugs, glands).
- Accessories with declared suitability for Al, contact paste, tightening torques from the data sheet.
- Protection selected the same way for copper and aluminium: the device rating must not exceed the cable's capacity, as explained in How to correctly select cable cross-sections.