RCD types AC, A, F and B: which one for heat pumps, EV chargers and inverters

The RCD type decides whether it trips on leakage currents from electronics. We compare Types AC, A, F and B and explain how to match an RCD to modern loads.

Contents
Residual current devices type AC, A, F and B with the loads they protect

A residual current device (RCD) protects against electric shock and reduces fire risk by disconnecting a circuit when part of the current leaks to earth. Besides the rated current and sensitivity (e.g. 30 mA), the type matters. It defines which residual current waveforms the RCD detects. In installations with heat pumps, EV chargers and inverters, choosing the type is as important as choosing the current rating.

The problem: leakage currents from electronics

Traditional loads such as heaters or incandescent lamps produce a sinusoidal residual current when insulation fails. Equipment with rectifiers and inverters can produce pulsating DC, mixed-frequency currents or even smooth DC. DC flowing through an RCD can magnetise its core and reduce its sensitivity, so it may fail to trip correctly even on an ordinary earth fault.

Types compared

TypeDetectsProduct standardTypical use
ACSinusoidal residual currentEN 61008-1 / 61009-1Simple resistive loads; used less and less
AAs AC + pulsating DC (including superimposed smooth DC up to 6 mA)EN 61008-1 / 61009-1Standard for socket, lighting and appliance circuits
FAs A + mixed-frequency currents (from single-phase inverters); smooth DC up to 10 mAEN 62423Washing machines, dishwashers, single-phase inverter heat pumps and air conditioners
BAs F + smooth DC and higher-frequency currentsEN 62423Three-phase inverter equipment, EV chargers without DC detection, some PV inverters

Each higher type includes the capabilities of the lower ones: a Type B RCD detects everything Types A and F do.

What a wrong choice costs

An RCD of the wrong type does not necessarily cause visible problems. The installation works and the RCD does not trip, but in a real earth fault it may not disconnect in time. So the type is matched to the load, not to whatever was in stock. Note too that a Type A or F RCD installed upstream of a Type B RCD can be blinded by the DC component from the loads the Type B device supplies. Manufacturers therefore recommend feeding circuits that need Type B from a separate branch that does not pass through a Type A RCD.

Matching the RCD to the equipment

Heat pumps and air conditioning

The equipment manufacturer's instructions decide, because only they know what residual current their inverter can produce. Single-phase inverter units often call for Type F or A; three-phase inverter units quite often for Type B. If the manual does not say, ask the manufacturer before fitting the RCD.

EV chargers

HD 60364-7-722 requires each connection point to have its own RCD with a rated residual current not exceeding 30 mA, of at least Type A, plus measures against DC fault current. Two solutions are possible:

  • a Type B RCD in the board;
  • a Type A (or F) RCD plus a residual direct current detecting device for DC above 6 mA (RDC-DD to EN IEC 62955), often built into the charger.

We cover this in detail in a separate article on protecting EV charging points.

PV inverters

If the inverter manufacturer declares that, by design, the inverter cannot feed DC fault current into the installation, a Type A RCD on the AC side is sufficient (where an RCD is required at all). Otherwise use Type B. Check the inverter manual.

Sockets, lighting, appliances

For socket-outlet circuits up to 32 A, HD 60364-4-41 requires additional protection by an RCD with IΔn not exceeding 30 mA. Type A is standard in homes; for washing machine or dishwasher circuits with inverter motors consider Type F.

RCD or RCBO

A residual current circuit breaker (RCCB) protects several circuits together, so one earth fault switches off the whole group. An RCBO combines residual current and overcurrent protection for a single circuit. See RCD vs RCBO for a comparison.

Nuisance tripping: where it comes from

An RCD that "trips for no reason" usually has a reason. The most common causes:

  • Summed leakage currents from many appliances with EMC filters (computers, power supplies, household appliances) approach the trip threshold. It is therefore recommended that total leakage downstream of an RCD stays below about 30% of its IΔn, another argument for spreading circuits across several RCDs.
  • A shared neutral between several RCD groups, or N connected to PE downstream of the RCD.
  • Moisture in outdoor boxes and sockets.
  • Surges: an SPD upstream of the RCD or a surge-resistant RCD helps.

Selectivity and Type S RCDs

When RCDs are in series (e.g. 300 mA feeding an outbuilding and 30 mA in its board), the upstream device should be selective (marked S, time-delayed) so that only the RCD nearest the fault trips.

Testing RCDs

The TEST button checks the mechanism; manufacturers recommend pressing it regularly, usually every few months. It does not replace measurements: trip time and current are measured with a tester at commissioning and during periodic verification under HD 60364-6.

Devices at automatics.pro

The residual current devices category includes the Legrand DX3 range in Types AC, A, F and B, in 2P and 4P versions, and the RCBO category includes DX3 RCBOs, also in Type F. Put together a full set of devices in the distribution board configurator.

Frequently asked questions

Can Type AC RCDs still be used?
Type AC detects only sinusoidal residual current, so it suits only simple loads without electronics. In new installations Type A is standard, and Type F or B for inverter-driven equipment.
Which RCD for a heat pump?
The one specified by the heat pump manufacturer. Single-phase inverter units often need Type F or A, three-phase inverter units quite often Type B.
Does an EV charger always need a Type B RCD?
Not always. HD 60364-7-722 allows a Type A RCD combined with a device detecting DC above 6 mA (RDC-DD), often built into the charger. Without such a device a Type B RCD is used.
What is the difference between Type F and Type A?
Type F also detects mixed-frequency residual currents typical of single-phase inverters and tolerates a larger smooth DC component (up to 10 mA).