··PolskiEnglish
Region and language

Prices include VAT of the delivery country.

CatalogueDelivery and paymentsRequest for quoteConfiguratorsArticles +48 793 996 171
Published: ·6 min read·Author:

Home consumer unit: how many circuits and which protective devices

A well-planned consumer unit pays off for years: one faulty circuit does not black out the house and there is room for PV and a charger. How to divide the installation and choose the devices.

Contents
Consumer unit in a single-family home and its circuits: lighting, induction cooker and heat pump

The consumer unit is the heart of a home installation: it distributes power to the circuits, protects cables against overload and short circuit, and protects people against electric shock. Protection requirements come from the HD 60364 series (PN-HD 60364 in Poland), but the division into circuits and the layout of devices are largely design decisions. Here are typical solutions that work in new houses and renovations.

The basic rule: more circuits, smaller consequences

Each circuit has its own overcurrent protection. The more circuits, the smaller the part of the house that loses power when a device trips, and the easier it is to find a fault. A house of about 150 m² typically has from a dozen to more than twenty circuits.

Typical circuit layout

CircuitTypical protectionTypical Cu cable
Lighting (ground floor, first floor, outdoor separately)B101.5 mm²
General sockets (a few rooms per circuit)B162.5 mm²
Kitchen worktop socketsB16 (1–2 circuits)2.5 mm²
Induction hob (three- or two-phase)per manual, e.g. 3 × B162.5 mm² or per manufacturer
Oven, dishwasher, washing machine, dryer, each separatelyB162.5 mm²
BathroomB16 (sockets), B10 (lighting)2.5 / 1.5 mm²
Boiler room / heat pumpper equipment manualcalculated
Outdoor sockets, gate, gardenB162.5 mm²
Spare: EV charger, PV, battery storageper designcalculated

These values are indicative. The protective device is always matched to the cable's current-carrying capacity, installation method and circuit length; see how to choose an MCB and how to select cable cross-sections.

Residual current protection

HD 60364-4-41 requires additional protection by an RCD with IΔn not exceeding 30 mA for, among others, socket-outlet circuits rated up to 32 A. In bathrooms HD 60364-7-701 requires it for all circuits. In practice, new houses have virtually all final circuits protected by 30 mA RCDs.

How many RCDs

  • One RCD for the whole house: cheapest, but one earth fault switches everything off and leakage currents from many appliances add up, causing nuisance tripping. Not recommended.
  • Several RCDs, each for a group of circuits: the common compromise, e.g. 3–4 four-pole or two-pole RCDs, with circuits spread so that the lighting and sockets of one area are not on the same RCD.
  • An RCBO per circuit: the best selectivity, as an earth fault trips only one circuit. More expensive but convenient. See RCD vs RCBO.

The RCD type follows the loads: Type A for ordinary circuits, often F or B for inverter-driven equipment. See RCD types AC, A, F and B.

Surge protection and AFDDs

A Type 2 surge protective device (SPD), or T1+T2 where there is lightning protection, goes in the main board and protects the electronics in the whole house. See our guide to surge protective devices.

Arc fault detection devices (AFDDs, EN 62606) detect arcing, for example in a damaged cable or a loose terminal, that MCBs and RCDs cannot detect. In a house they are recommended in bedrooms and in circuits where a fire would have particularly serious consequences, such as timber structures.

Main switch, indication, spare space

  • A main isolator at the start of the board lets you safely disconnect the whole installation.
  • Phase indicator lamps help with diagnostics.
  • Spare space: plan at least 20–30% free modules. PV, an EV charger or battery storage usually arrive a few years later. See our articles on protecting EV charging points and PV AC/DC distribution boards.
  • Circuit labelling: every device labelled and a diagram inside the board door.

Choosing the enclosure

Flush-mounted boards suit living areas; surface-mounted ones suit garages and boiler rooms. The number of rows follows the number of modules (a single-pole device usually takes 1 module, a 4P RCD 4 modules, a 4P SPD 4 modules) plus spare. A house with a dozen or more circuits, several RCDs and an SPD usually needs 3–4 rows of 12 or 18 modules. For assembly see how to assemble a distribution board and wiring and connections in distribution boards.

Device order in the board

A clear layout makes installation, service and later extensions easier. A typical order from the supply:

  1. main isolator (or main circuit breaker),
  2. surge protective device with its backup protection if needed,
  3. phase indicator lamps,
  4. RCDs, each followed by its group of MCBs,
  5. circuits with their own RCBOs or supplied outside the group RCDs (e.g. an EV charger),
  6. control devices: contactors, relays, time switches.
Typical device order in a home distribution board from the supply: main isolator, SPD, phase lamps, RCDs with MCB groups, RCBO circuits, control devices.1. Main isolator (or main breaker)1Main isolator (or main breaker)2. Surge protective device (SPD)2Surge protective device (SPD)3. Phase indicator lamps3Phase indicator lamps4. RCD followed by its group of MCBs4RCD followed by its group of MCBs5. Circuits with RCBOs or outside RCDs (e.g. EV)5Circuits with RCBOs or outside RCDs (e.g. EV)6. Control: contactors, relays6Control: contactors, relays
Device order in the board from the supply side — diagram of the list above.

Busbars (comb bars) speed up assembly and tidy the connections along a row. The neutral conductors of each RCD group go to a separate neutral bar or terminal; a shared neutral bar for several RCDs is a frequent cause of unexplained tripping.

Upgrading an old installation

Older houses often have a few fuses and no residual current protection. When replacing the board, check the condition of the cables (especially aluminium and two-core cables without a protective conductor), separate N and PE at the right point and divide the circuits so that the new board really improves safety. Simply swapping fuses for breakers does not fix a faulty installation. After the upgrade, carry out the verification tests required by HD 60364-6.

Put your board together

The fastest way to plan a board is the distribution board configurator: choose the circuits and it suggests the devices and enclosure. Components are in modular distribution boards (including Legrand Practibox S), Legrand DX3 MCBs and RCDs, Legrand ON 300 surge protective devices and AFDDs.

Frequently asked questions

How many circuits should a house have?
There is no single number. A house of about 150 m² typically has from a dozen to more than twenty circuits: separate ones for lighting, socket groups, kitchen, bathroom and each large appliance, plus spare.
Is one RCD enough for the whole house?
It is not recommended. One earth fault would switch off the whole house and leakage currents from many appliances add up. Split the circuits across several RCDs or use an RCBO per circuit.
What protection for a socket circuit?
Most often a B16 breaker with 2.5 mm² Cu cable and 30 mA RCD protection. The rating is always checked against the cable capacity and installation method.
How much spare space should a board have?
In practice 20–30% free modules, to fit future protection for PV, an EV charger or battery storage.

← All articles