Protecting EV charging points at home and at work: breaker, RCD, cable and board
An EV charger is a high-power load that runs for hours. What HD 60364-7-722 requires, how to choose the breaker, RCD and cable, and what to prepare in the board.

An electric vehicle charging point is a special load: it draws high current for many hours, often sits outdoors and connects to a vehicle with its own electronics. That is why installations supplying charging points have their own part of the wiring standard, HD 60364-7-722 (PN-HD 60364-7-722 in Poland). Here is how to protect a charger in practice, at home and in a company car park.
Charger power and the supply
Before choosing protection, check the supply capacity and the main fuse. Typical AC charging powers:
| Power | Supply | Current |
|---|---|---|
| 3.7 kW | single-phase, 230 V | 16 A |
| 7.4 kW | single-phase, 230 V | 32 A |
| 11 kW | three-phase, 400 V | 16 A per phase |
| 22 kW | three-phase, 400 V | 32 A per phase |
If there is little spare capacity, consider a charger with dynamic load management that reduces the charging current when other large loads (induction hob, heat pump) are running.
HD 60364-7-722 in a nutshell
- A dedicated circuit for each connection point; never connect a charger to a general socket circuit.
- Each connection point has its own overcurrent protection.
- Each connection point has its own RCD with IΔn not exceeding 30 mA, at least Type A.
- DC fault protection: a Type B RCD, or a Type A/F RCD combined with a device detecting DC above 6 mA (RDC-DD to EN IEC 62955). Many chargers have an RDC-DD built in; the datasheet will say so.
Check the charger datasheet: "6 mA DC protection" or "RDC-DD" means a Type A RCD in the board is enough. Without it you need a Type B RCD. Some chargers also include a full set of protection (e.g. an RCBO); the board then only protects the supply cable.
Choosing the circuit breaker
The breaker rating follows the charging current and the cable's current-carrying capacity (In ≥ circuit current, In ≤ cable capacity for the installation method). Charging is a continuous load, so do not size to the limit: for an 11 kW (16 A) charger a 3-pole 16 A or 20 A breaker is typical, for 22 kW (32 A) a 32 A or 40 A breaker, always as the charger manual specifies. Curve C or B is most common; see how to choose an MCB.
Choosing the supply cable
The cable size depends on current, installation method, temperature and voltage drop. On long runs to a garage or carport, voltage drop often drives a larger size. As a rough guide, 16 A circuits typically use 2.5–4 mm² Cu and 32 A circuits 6–10 mm² Cu, but always calculate for the actual route; see how to select cable cross-sections. Use cables rated for direct burial underground and UV-resistant cables outdoors.
Surge protection
The charger and the car are expensive electronics. If the main board has no surge protective device, add one when installing the charger; for a long circuit to an outdoor charger, check whether an extra SPD at the charger is needed. See our guide to surge protective devices.
The board and mounting location
- Reserve space in the board for a 1P+N or 3P+N breaker, the RCD (or RCBO) and possibly a sub-meter, useful for billing company car charging.
- An outdoor charger needs a suitable IP rating and IK impact rating; see understanding IP ratings.
- In a company car park, plan cable routes with spare capacity for more charging points.
Example bill of materials for a home (11 kW)
| Item | Example |
|---|---|
| Charger | Three-phase 11 kW wallbox with 6 mA DC detection |
| Overcurrent protection | 3P breaker (rating per charger manual, e.g. 16–20 A) |
| Residual current protection | 4P 30 mA Type A RCD (or Type B if the charger has no DC detection) |
| Cable | 5-core Cu, size per current-carrying capacity and voltage drop |
| Surge protection | Type 2 SPD in the main board |
Socket charging or a wallbox
A car can be charged with a portable charger from a socket (mode 2) or from a charging station permanently connected to the installation (mode 3). Charging from an ordinary household socket for many hours at close to rated current puts heavy stress on the socket and plug contacts. If mode 2 will be used regularly, provide a socket designed for EV charging or an industrial socket on a dedicated circuit. For daily charging a mode 3 station is more convenient and safer.
Chargers, PV and tariffs
Connected chargers can charge the car from surplus PV energy or during cheaper tariff hours. This usually needs a meter or current transformers measuring power flow at the supply point. If you plan to use it, leave space in the board for an energy meter and run a communication cable to the charger during the first installation.
Products at automatics.pro
The EV charging stations category includes Legrand Green'up chargers (including wallboxes with 6 mA DC protection) and Plexo charging sockets. Devices are in MCBs, residual current devices (Legrand DX3, including Type B) and surge protective devices; plan the whole board in the distribution board configurator. RCD types are compared in detail in RCD types AC, A, F and B.