Choosing a distribution board enclosure: flush, surface, floor-standing, IP and IK
The enclosure decides how safe, durable and serviceable a board is. Enclosure types, materials, IP and IK ratings and how to work out the space you need.

A board enclosure protects the devices against foreign objects and water, people against contact with live parts, and the whole assembly against mechanical damage. It also affects the internal temperature and therefore how the devices perform. Empty enclosures for low-voltage assemblies are covered by EN 62208, IP degrees of protection by EN 60529 and IK impact ratings by EN 62262. Here are the decisions to make when choosing one.
Mounting type
| Type | Use | Watch out for |
|---|---|---|
| Flush (recessed) | Flats, houses, offices: appearance and space saving | Recess depth, load-bearing and fire walls, cable space in the wall |
| Surface-mounted | Garages, boiler and plant rooms, refurbishments | Cable entry (glands, trunking), IP at the entries |
| Wall-mounted steel cabinet | Medium-size industrial and control boards | Wall load capacity, door swing, access to the interior |
| Floor-standing | Main boards, high currents, many sections | Plinth, transport, working space in front, extension in a suite |
Material: plastic or steel
- Plastic (e.g. Practibox S modular boards, sealed enclosures): light, insulating (often Class II), corrosion-free. Good for homes and damp rooms.
- Reinforced polyester (e.g. Marina enclosures): resistant to chemicals and outdoor conditions, insulating; used in industry and outdoors.
- Painted steel (e.g. Atlantic cabinets, the XL3 system): mechanically strong, good heat dissipation, must be connected to the protective conductor.
- Stainless steel: food and chemical industries, aggressive environments, frequent washing.
IP degree of protection
The IP code has two digits: the first for protection against solid objects and contact (0–6), the second against water (0–9). Typical values for boards:
| Location | Typical rating |
|---|---|
| Flat, office (dry) | IP30–IP40 |
| Garage, basement, plant room | IP41–IP44 |
| Outdoors under cover, construction site | IP44–IP55 |
| Outdoors uncovered, wash-down areas | IP65–IP66 |
The IP rating applies to a closed, correctly assembled enclosure. Every cable entry without a suitable gland and every hole cut reduces it. See understanding IP ratings and IP44 vs IP54.
IK impact resistance
The IK code (EN 62262) gives the impact energy the enclosure withstands:
| Code | Impact energy | Example use |
|---|---|---|
| IK06 | 1 J | Residential interiors |
| IK07 | 2 J | Offices, corridors |
| IK08 | 5 J | Plant rooms, garages |
| IK09 | 10 J | Halls, warehouses, public areas |
| IK10 | 20 J | Areas exposed to vandalism, trolley traffic, outdoors |
Transparent doors often have a lower rating than solid doors; where mechanical damage is likely, choose solid or reinforced doors.
How much space you need
Modular boards
Add up the module widths of the devices (a 1P breaker usually takes one 17.5 mm module, a 4P RCD 4 modules, a 4P SPD 4 modules, terminal blocks depending on the model) and add spare, usually 20–30%. Allow for N and PE bars and room to bend the conductors.
Cabinets
In industrial cabinets, what counts is not only the mounting plate area but also space for slotted trunking, terminal blocks and the bending radius of supply cables. Large cables need room at the entry; a cabinet that is too shallow makes connection difficult.
Heat in the enclosure
Devices give off heat, and manufacturers state their power loss in watts. A closed high-IP enclosure dissipates heat less well than a ventilated one. When the internal temperature exceeds what the devices allow, breakers trip at lower currents and their life shortens. Solutions:
- a larger or metal enclosure,
- spreading out high-loss devices,
- filtered ventilation grilles (keeping the required IP),
- thermostat-controlled fans or a cabinet air conditioner in harsh conditions.
Switchboard system manufacturers give permissible power losses for their enclosures; these are used for temperature-rise verification under EN 61439, covered in switchgear assemblies to EN 61439.
Other criteria
- UV resistance: outdoor plastic enclosures must be designed for it.
- Locks: key, cylinder lock, padlock hasp; lockable doors where ordinary persons have access.
- Protection class: insulating enclosures allow a Class II board.
- Appearance: in front-of-house areas, colour and door finish matter.
Cable entry and glands
Plan the position and method of cable entry together with the enclosure. Surface and industrial enclosures use cable glands matched to the cable diameter and required IP; modular boards use membrane grommets or knockouts. Cables entering from the top in damp rooms can lead water inside, so in such locations bottom or side entry with a drip loop is better. Large cabinets use removable gland plates that can be machined outside the cabinet. Glands and cable clamps are in the cable glands, clamps and ties category.
Example selections
| Situation | Suggestion |
|---|---|
| Flat, 12–20 circuits | Flush plastic board, 3–4 rows, IP30–40, solid or transparent door |
| Garage of a house | Surface plastic board IP41–44, glands on every entry |
| Production hall | Steel cabinet IP55–66, IK08–IK10, mounting plate, thermostat-controlled ventilation |
| Outdoor supply (car park, site lighting) | UV-resistant polyester enclosure IP65–66, lockable |
When choosing an enclosure, think about the board's whole life cycle. An enclosure that opens easily, with convenient access to terminals and room for labels, shortens inspections and repairs. Removable covers and mounting plates make extensions possible without dismantling everything, and system accessories from the same manufacturer (busbars, supports, blanking covers) let you add devices years later without making parts. A cheaper enclosure without these features often costs more over its life. Before buying, check in the manufacturer's catalogue which accessories exist for the enclosure range and whether the range is still being developed.
Enclosures at automatics.pro
The modular distribution boards category includes Legrand Practibox S and Nedbox; enclosures and cabinets includes Atlantic and Marina cabinets and the XL3 system; and enclosure climate control covers heat management accessories. Choose the enclosure together with the devices in the distribution board configurator.