Surge protective devices SPD type 1, 2 and 3: when to use them and how to select

Type 1, Type 2 or T1+T2? How surge protection works in a low-voltage installation, which SPD ratings matter and how to avoid typical installation mistakes.

Contents
Surge protection – lightning strike on an air terminal, SPD modules, earth electrode and protected equipment

Transient overvoltages in low-voltage installations come from lightning, both direct and nearby strikes, and from switching operations in the grid. They mostly damage electronics: power supplies, heat pump controllers, PV inverters, EV chargers and AV equipment. A surge protective device (SPD) limits the voltage to a level the equipment can withstand and diverts the surge current to earth. SPD selection is covered by HD 60364-4-443 (when protection is needed), HD 60364-5-534 (selection and installation) and EN 61643-11 (requirements and tests for SPDs); in Poland these are published as PN-HD and PN-EN standards.

Type 1, Type 2, Type 3: the differences

Type (test class)Test impulseKey ratingTypical location
Type 1 (T1)10/350 µs, part of a lightning currentIimpOrigin or main board of a building with a lightning protection system or overhead supply
Type 2 (T2)8/20 µs, induced and switching surgesIn, ImaxMain or sub-distribution board
Type 3 (T3)Combination waveUocNext to the protected equipment (socket, power strip)

T1+T2 devices combine both functions, so a single device can be used in the main board of a house.

When surge protection is required

HD 60364-4-443 requires protection against transient overvoltages where an overvoltage could affect human life, public services, commercial or industrial activity, or large numbers of people. In other cases the decision follows the risk assessment described in the standard. In practice, new installations, especially with a heat pump, PV or EV charger, get an SPD in the main board as standard, as its cost is small compared with the equipment it protects.

When Type 1 is needed

  • The building has an external lightning protection system (LPS): use a Type 1 (or T1+T2) SPD at the origin or in the main board. Lightning protection is designed to the EN 62305 series.
  • The building is supplied by an overhead line: Type 1 is recommended, because part of a strike to the line can reach the installation.

Without an LPS and with an underground cable supply, a Type 2 SPD in the main board is usually enough.

Ratings to check

  • Uc, maximum continuous operating voltage. For 230/400 V TN systems choose Uc of at least 1.1 × U0, i.e. at least 253 V; 275 V or 320 V devices are used in practice.
  • Up, voltage protection level. It must be lower than the impulse withstand of the protected equipment. For 230/400 V installations HD 60364-5-534 requires Up at the origin of the installation not to exceed 2.5 kV.
  • In / Imax (Type 2), nominal and maximum discharge current. HD 60364-5-534 requires In of at least 5 kA per protection mode.
  • Iimp (Type 1), impulse current. If not determined by risk analysis, at least 12.5 kA per protection mode.
SPD requirements per HD 60364-5-534
ParameterRequirement
Uc (230/400 V, TN)≥ 1.1 × U0 = 253 V; in practice 275 V or 320 V
Up at the origin of the installation≤ 2.5 kV
In (Type 2)≥ 5 kA per protection mode
Iimp (Type 1), without risk analysis≥ 12.5 kA per protection mode
SPD connecting leads≤ 0.5 m in total
Cheat sheet: minimum SPD parameters for a 230/400 V installation discussed in the article.

Installation in the board: common mistakes

Connecting leads too long

The voltage seen by the equipment is the SPD's Up plus the voltage drop on its leads. Keep the leads from the phase busbar to the SPD and from the SPD to the PE bar as short as possible; HD 60364-5-534 recommends a total length not exceeding 0.5 m. Mounting the SPD next to the PE bar and using V-wiring (in and out of the same terminal) helps.

No SPD backup protection

At the end of its life an SPD may short-circuit. The manufacturer states the maximum fuse or breaker rating upstream. If the main fuse is larger, the SPD gets its own backup protection.

SPD downstream of an RCD

In TN systems SPDs are usually installed on the supply side of the RCD. If the SPD has to be downstream, use a surge-resistant RCD (e.g. type S).

Equipment too far away

On long circuits (roughly more than 10 m from the SPD) protection becomes less effective. For sensitive electronics far from the board, add a Type 2 SPD in the sub-board or a Type 3 SPD at the equipment.

Example selection for a single-family house

SituationSolution
Cable supply, no LPS, TN-C-SType 2 SPD, 3P+N or 4P, Uc 275–320 V, in the main board
LPS present or overhead supplyT1+T2 SPD in the main board
PhotovoltaicsAn additional DC-side SPD matched to the string voltage (e.g. 1000 V DC)
AV equipment, computersType 3 SPD in the socket or power strip

Checking and replacing SPDs

An SPD wears with every significant surge. Most modular devices have a status indicator (a window that changes colour) and plug-in cartridges, so after operation you do not have to replace the whole base. Check the indicators after storms and during periodic inspections. Some models have a remote signalling contact that can be wired into the building automation system so that a worn SPD does not go unnoticed.

Remember the signal lines too: a surge can enter a building not only through the power cables but also via the aerial, telecom line or gate cables. Full protection of electronics uses SPDs designed for those lines.

SPDs at automatics.pro

The surge protective devices category includes the Legrand ON 300 range as Type 2 (e.g. Imax 12, 20 and 40 kA, Uc 275 or 320 V) and T1+T2 (Iimp 12.5 kA, Uc 320 V) in 1P+N, 3P, 3P+N and 4P versions, plus replacement cartridges. Type 2 SPDs for 1000 V DC are in photovoltaics, and external lightning protection in lightning protection.

Plan space for the SPD from the start: the distribution board configurator lets you add it together with the other devices. For more on protection see MCBs and RCDs in the EU.

Frequently asked questions

Does a house without a lightning rod need a Type 1 SPD?
Usually not. With an underground cable supply and no external lightning protection, a Type 2 SPD in the main board is normally sufficient. Type 1 is used where there is an LPS and recommended for overhead supplies.
Which Uc should I choose for a 230/400 V installation?
In TN systems Uc should be at least 1.1 × U0, i.e. 253 V. In practice SPDs with Uc of 275 V or 320 V are used.
How long can the SPD connecting leads be?
As short as possible. HD 60364-5-534 recommends a total length of the leads from the phase conductor to the SPD and from the SPD to the PE bar of no more than 0.5 m.
Does the SPD go before or after the RCD?
In TN systems usually before the RCD, on the supply side. If it has to go downstream, use a surge-resistant RCD such as type S.