Photovoltaic installations: AC/DC distribution boards and protection step by step
The DC side of a PV system follows different rules from an ordinary 230 V installation. Devices for the DC and AC boards, voltage ratings and the most common mistakes.

A photovoltaic installation has two parts with very different properties. On the DC side, from the modules to the inverter, direct current flows at several hundred volts, or 1000 V and more in larger systems. On the AC side, the inverter feeds the ordinary 230/400 V installation. Requirements for PV installations are set out in HD 60364-7-712 (PN-HD 60364-7-712 in Poland). Here we go through the devices on both sides and what to watch out for.
Why DC is harder
Alternating current passes through zero a hundred times a second, which helps extinguish the arc when switching. Direct current has no zero crossing, so an arc drawn when switching under load is stable and can damage the device or start a fire. On the DC side use only devices designed for DC, with a DC voltage rating at least equal to the maximum string voltage. An ordinary AC breaker or switch is not suitable.
Note: PV modules produce voltage whenever light falls on them. Disconnecting the inverter does not remove voltage from the module cables. Plan any work on the DC side accordingly.
DC side: what goes in the DC board
DC switch-disconnector
It isolates the PV array from the inverter for work and service. Many inverters have one built in; if not, or if the inverter is far from the modules, an external DC switch-disconnector is used. Key ratings: DC voltage (e.g. 800 V or 1000 V DC), rated current and number of poles.
gPV fuses
When several strings run in parallel, a faulty string can be back-fed by the others. If that reverse current can exceed the module's reverse current rating (from the module datasheet), strings are protected by gPV fuses. In small systems with one or two strings per MPPT input fuses are usually unnecessary; the calculation for the actual modules decides.
DC surge protective device
A DC-side SPD protects the inverter inputs against surges induced in the long module cables. It is selected for the maximum PV array voltage (e.g. 600 V or 1000 V DC) and installed as close to the inverter as possible; with long distances to the modules a second SPD near the modules is considered. SPDs for PV are tested to the standard for SPDs in photovoltaic installations (EN 61643-31).
Solar cables
The DC side uses cables designed for PV, such as H1Z2Z2-K (EN 50618), resistant to UV and high temperature. Run the plus and minus conductors close together to keep the induction loop small.
AC side: inverter protection
- Circuit breaker in the inverter circuit, sized for the inverter's maximum output current and the cable capacity, as the manufacturer specifies.
- RCD, where required, with the type depending on the inverter. If the manufacturer declares that the inverter cannot feed DC fault current into the installation, Type A is enough; otherwise Type B. See RCD types AC, A, F and B.
- AC surge protective device: Type 2 (or T1+T2 if the building has lightning protection) in the main board. See surge protective devices.
- Isolator or breaker for disconnecting the inverter from the grid, easily accessible and labelled.
Enclosure and labelling
DC boards are often installed outdoors or in hot loft spaces. What matters is the IP rating (usually IP65 outdoors), UV resistance and the enclosure's DC voltage rating. Every board and junction box with DC parts carries a warning that live parts may remain energised after the inverter is disconnected. A notice at the supply point and main board that a PV system is present helps service staff and firefighters.
Common mistakes
- An AC device, or one with too low a DC rating, on the DC side.
- Ignoring low temperatures: module voltage rises in frost, so string voltage is calculated for the lowest expected temperature.
- Reversed polarity when connecting a polarised DC switch or breaker.
- The wrong RCD type on the AC side.
- Large DC cable loops that increase induced surges.
Example for a house (about 10 kW, three-phase inverter, 2 strings)
| Side | Devices |
|---|---|
| DC | 1000 V DC switch-disconnector (if not built into the inverter), Type 2 PV SPD 1000 V DC, IP65 PV enclosure |
| AC | 3P breaker per inverter manual, RCD per inverter manufacturer's declaration (A or B), Type 2 SPD in the main board |
| Cables | H1Z2Z2-K on the DC side; AC cable sized for current and voltage drop |
Commissioning and documentation
Before start-up a PV installation is inspected and tested, including continuity of protective conductors, insulation resistance of the DC circuits, open-circuit voltage and short-circuit current of the strings, and correct polarity. The results, together with a diagram (modules per string, device types, cable sizes), go into the as-built documentation. Grid connection follows the distribution system operator's procedure and document requirements.
PV devices at automatics.pro
The photovoltaics category includes Legrand Plexo3 PV enclosures (1000 V DC, IP65), PV switch-disconnectors (e.g. 32 A and 63 A, 1000 V DC), PV circuit breakers for 800 and 1000 V DC, gPV fuse links and Type 2 SPDs for 1000 V DC. AC-side devices are in MCBs, residual current devices and surge protective devices; plan the board in the distribution board configurator.